Siemens’ Tips for Panel Builders Series – Part 2: Class 2 Power Supplies for 24V DC Circuits

PBUS Siemens logo 400

September 8, 2020

When control equipment is used in the U.S., the UL standards have to be complied with in respect of safety and fire protection. The standards-compliant configuration of the control panel plays a major role here. Control circuits according to NEC Class 2 must be limited in power to 100 VA. By selecting the right power supply and fuse protection, acceptance can be simplified significantly and costs can also be saved.


Practical tips for you!

Every item of control equipment is checked and approved in the U.S. by the competent AHJ inspector (Authority Having Jurisdiction). The AHJ inspector does not have to accept the components in safe NEC Class 2 control circuits (UL 508 § 2.7) which is why non-listed UL devices may also be used. On the other hand, components with the approval “…for use with Class 2 only…” shall only be connected to NEC Class 2 circuits. An NEC Class 2 control circuit may be fed out of the control panel if it is marked at the terminals for that purpose and is laid separately to other circuits.

Control circuits according to NEC Class 2 can be implemented with various concepts:

The Conventional Version: Use of NEC Class 2 Power Supplies Siemens2 2

Power supplies according to NEC Class 2 are characterized by the fact that the output power is limited to 100 VA even if a fault occurs.  A power supply unit is required with multiple control circuits. If the system is expanded, an NEC Class 2 control circuit can easily be implemented by means of an additional power supply unit.

The Version for High Availability: Redundancy Modules with Power Limitation Siemens2 3

When SITOP redundancy modules are used with NEC Class 2 output, more powerful central power supply units can be used as they limit the power to max. 100 VA. Connection is made either at one power supply in order to distribute the 24 V supply only to NEC Class 2 feeders, or at two central power supplies to additionally ensure a higher availability of the 24 V supply. In this case, the redundancy module decouples the two power supply units and, if one power supply unit fails, the redundancy module supplies the control circuit via the intact power supply unit.

The Version with Integrated Cable Protection: Selectivity Modules with Multiple NEC Class 2 Outputs Siemens2 4

NEC Class 2 load feeders can also be implemented with special selectivity modules. In this case, a central 24 V DC power supply feeds one or multiple selectivity modules, the output channels of which are limited to a power of 100 VA. The advantage of this configuration is that both the power limitation to NEC Class 2 and selective protection of the outputs against overload or short circuit can be implemented. A faulty feeder is immediately de-energized and all other feeders continue to be supplied without interruption. Even a PLC that bridges a power failure for just a few milliseconds continues to run without any problem. When SITOP NEC Class 2 selectivity modules are used no additional short-circuit protection devices have to be installed in the four NEC Class 2 feeders.

Check out a video tutorial here!

Source

Related Articles

Network Infrastructure Featured Product Spotlight

PBUS 14 Panduit logo 400

This webinar presented by Beth Lessard and Keith Cordero will be highlighting three Panduit solutions that will optimize network equipment and cabling to ensure that your spaces are efficiently and properly managed to support ever-evolving business needs of today and beyond. Products that will be featured include PanZone TrueEdge Wall Mount Enclsoure, Cable Managers, and Adjustable Depth 4-Post Rack.

REGISTER HERE


Editor’s Pick: Featured Product News

Siemens: SIMOVAC Non-Arc-Resistant and SIMOVAC-AR Arc-Resistant Motor Controllers

The Siemens SIMOVAC medium-voltage non-arc-resistant and SIMOVAC-AR arc-resistant controllers have a modular design incorporating up to two 12SVC400 (400 A) controllers, housed in a freestanding sheet steel enclosure. Each controller is UL 347 class E2, equipped with three current-limiting fuses, a non-load-break isolating switch, and a fixed-mounted vacuum contactor (plug-in type optional for 12SVC400). The enclosure is designed for front access, allowing the equipment to be located with the rear of the equipment close to a non-combustible wall.

Read More


Sponsored Content
Electrify Your Enterprise

Power is vital to production, and well-designed control cabinets are key. Allied Electronics & Automation offers a comprehensive collection of control cabinet solutions including PLCs, HMIs, contactors, miniature circuit breakers, terminal block connectors, DIN-rail power supplies, pushbutton switches, motor starters, overloads, power relays, industrial Ethernet switches and AC drives engineered to keep your operations running safely, reliably and efficiently.

Learn more HERE.


Products for Panel Builders

  • Kooltronic: New DSP28 3,000 BTU/H Slim-Depth Access Series High Capacity Cooling Unit

    Kooltronic: New DSP28 3,000 BTU/H Slim-Depth Access Series High Capacity Cooling Unit

    Kooltronic, Inc. of Pennington, NJ has added a new 3,000 BTU/H model to its Access Series line of slim-depth electrical enclosure air conditioners – the DSP28 AC unit. Kooltronic has expanded its Access Series line of slim-depth air conditioners with a higher-capacity model. The new 3,000 BTU/H Access Series DSP28 AC unit rounds out the… Read More…

  • Weidmuller: New Basic Line Series B Unmanaged Switches Offer Cost-Effective Alternative

    Weidmuller: New Basic Line Series B Unmanaged Switches Offer Cost-Effective Alternative

    Weidmuller USA has recenty introduced Basic Line Series B — cost-effective unmanaged switches ensuring high EMC compatibility, extended temperature ranges, and numerous certifications for a wide range of industrial applications. This new solution from Weidmuller supports Profinet CC-A and Ethernet/IP networks with features including Quality of Service (QoS), broadcast storm protection, and LLDP filtering. Designed for maximum… Read More…